Preferred ratings shown below. Custom output voltages available in 0.1V increment from the minimum voltage listed to the maximum voltage listed; contact sales.
Model Number (Final ordering #/Part No to be defined)
Voltage (V)
Current (A)
Power (W)
RFQ
GTM96600-6048-R2L*
48
1.25
60
GTM96600-60VV.V-R2L-XXXX
CUSTOM
CUSTOM
CUSTOM
* (Final ordering #/Part No to be defined)
Specifications
Input
Input Voltage:
Specified: 90-264VAC, Nameplate: 100-240VAC 100% rated load current for 90-264VAC 85% rated load current for 85-264VAC 100% rated load current for 110-370VDC
Complies with EU 2011/65/EU and China SJ/T 11363-2006
Note 1:
Regarding operating temperature a. See below de-rating table for output power capability at alternate temperature b. Extended low-end temperature range available as a custom option
Safety
Dielectric Withstand Voltage:
4000VAC or 5656VDC from input to output 3000VAC or 4242VDC from input to earth (Class I models only)
Touch Current:
Class I: 20µA max. Class II: 85µA max. Class II F2: 20µA max.
Earth Leakage Current
Class I: 300µA max. Class II: N/A
Means of Protection:
2 x MOPP
Output Isolation Options:
Class I: C6 or C14 inlet (output negative tied to Earth contact) Class II: C8 or C18 inlet Class II FE: C6 or C14 inlet (output isolated from Earth contact) Review isolation options by reading our white paper PSU Isolation and Identity.
Earth Continuity Test:
< 0.1Ω between earth pin (on AC inlet) and PCB termination point (Class I models only)
Compliant Standards:
See listing at end of this datasheet for specific standards
Class B, FCC Part 15, Class B (with resistive load)
Radiated Emissions:
Class B, FCC Part 15, Class B (with resistive load)
Harmonic Current Voltage Distortion:
EN61000-3-2, Class A
Voltage Fluctuations/Flicker:
EN61000-3-3
Electrostatic Discharge (ESD) Immunity:
EN61000-4-2, 10KV contact discharge, 20KV air discharge
Radiated RF Immunity:
EN61000-4-3, 10V/m 80-1000MHz, 3V/m 1-2.7GHz, 80% 1KHz AM
EFT/Burst Immunity:
EN61000-4-4, 4KV/100kHz.
Line Surge Immunity:
EN61000-4-5, 2KV differential, 4KV common-mode
Conducted RF Immunity:
EN61000-4-6, 3VRMS, 80% 1KHz AM
Power Frequency Magnetic Field Immunity:
EN61000-4-8, 3A/m
Voltage Dip Immunity:
EN61000-4-11
Enclosure
Housing:
High impact plastic, 94V0 polycarbonate, non-vented
AC Input Mechanical Options:
Desktop: C6, C7, C14, or C18 inlet Hybrid: Desktop inlet or changeable blades for wall-plug-in style, Class I or Class II input
Markings:
Label and/or pad printed and/or laser-etched into case
Special Options
Removal of LED (cost reduction or aesthetic purpose)
Custom cordsets, various cordage types, and connector types
Custom markings
Short term output surge capability for motors or other high peak current loads. (Available up to 120W for 1 second at nameplate voltage range. Higher levels possible for limited input voltage range, or larger allowed voltage dip.)
Reduced leakage current
Tightened output voltage tolerance
Reduced output ripple level
Reduced output power rating
High reliability PCB laminate with plated through-holes for IPC610 Class 2 compliance
Low temperature option, down to -40°C
Special housing and cordset colors
"Back EMF" upgrade, for motor loads and other high inductance applications with reverse energy flow requirements
Improved ingress protection (IP) rating
Output Connectors
Several output connector options are available with various output current ratings. GlobTek can supply 10A rated 2.1mm and 2.5mm style DC Power Jacks, to complement our 10A output rated 2.1mm and 2.5mm DC power plugs used on our output cordsets.
This series of Interchangeable Blade products may be used with Proprietary Interchangeable Blades as described below or with standard international power cords.
Optional INPUT BLADES: R-Socket: below are available blades configurations which are "not included" (unless stated above); may be purchased separately, packaged with power supply, or as a separate "R-KIT" if specified
Standard Cordsets Below are standard cordsets which are "not included" (unless stated above); these may be purchased separately or packaged with the power supply. Contact your Sales Engineer if the style required is not shown below. Many more available in different lengths, colors or cable material.
Contact GlobTek for your specific requirements or custom solutions.
Approvals
Below follows a link to the latest regulatory certifications and marks for this specific product. National standards as well as certification schemes are constantly changing and so is the set of certification marks and symbols applicable to this product. Various standards, marks and symbols, and certificates are subject to change at any time without notice.
Additional standards or unique country certifications are available upon request. Please contact Globtek to request a quotation.
Logo
Description
Medical 4th Ed.
EN/IEC 60601-1-2, 4th Edition (Please visit EMC reports for further info)
No Logo Applicable
CB for IEC 60335-1:2010+A1
Book 60335 up to 36 Volts
Class 2 Power Unit
Class 2 Power Units [UL 1310:2011 Ed.6 +R:12Dec2014] Power Supplies With Extra-Low Voltage Class 2 Outputs [CSA C22.2 No.223:2015 Ed.3] up to 5A
Japan: Voluntary Control Council for Interference (VCCI)
CHINA SJ/T 11364-2014, China RoHS Chart: http://www.globtek.com/pdf/F-GT-DJD-8.4.1-006%20China%20RoHS%20Declaration%205-20-22.pdf
RoHS
Specifications of directive 2011/65/EU Annex VI (ROHS-2) with amendment 2015/863-EU (ROHS-3) http://www.ce-mark.com/Rohs%20final.pdf
Efficiency: complies to section 301 of Energy Independence and Security Act (EISA) complies with Energy Star tier 2 (North America), ECP tier 2 (China), MEPS tier 2 (Australia), Code of Conduct (Europe)
No Logo - Molded in Case
Double Insulation - Mark is on the label or Molded in the case
Test standard: EN 55032:2012+AC:2013 EN 61000-3-2:2014 EN 61000-3-3:2013 EN 55024:2010 EN 60601-1-2:2015
仅适用于海拔2000米以下地区使用
CCC to GB4943.1-2011 GB9254-2008 GB17625.1-2012
No Logo Applicable
CB for IEC 60950-1:2005+A1+A2
GMA-512684-EA
RCM certificate ; Australia and New Zealand Regulatory Compliance, Mark (http://rcm.standards.org.au/rcmfaq/rcmfaq.htm
LPS
Limited Power Source 60950
Indoor Use Only - Mark is on the label or Molded in the case
JAPAN TUV R-PSE, Cert. No. JD 50469658, to J62368-1(H30) , J55032(H29),J3000(H25)[15V or less]. Please reference the following website for guidelines on PSE regulations: https://www.globtek.com/r2/Szj4Vb
JAPAN TUV R-PSE, Cert. No. JD 50313287, to J60950-1(H26) , J55022(H22),J3000(H25)[DC15?30V]. Please reference the following website for guidelines on PSE regulations: https://www.globtek.com/r2/Szj4Vb
JAPAN TUV R-PSE, Cert. No. JD 50313287, to J60950-1(H26) , J55022(H22),J3000(H25)[DC30?60V]. Please reference the following website for guidelines on PSE regulations: https://www.globtek.com/r2/Szj4Vb
Information Technology Equipment Safety Part 1: General Requirements >Valid without technical revision:01Jan2022< [UL 60950-1:2007 Ed.2 +R:14Oct2014
No Logo Applicable
IEC 60601-1:2005+A1 IEC 60601-1-11:2015
S-Mark Certificate EN 60601-1:2006+A1+A12, EN 60601-1-11:2015
Certification # TC RU C-US.AR46.B.79113 Custom Union of Russia, Belarus and Kazakhstan
Class 2 Power Units [UL 1310:2011 Ed.6 +R:12Dec2014] Power Supplies With Extra-Low Voltage Class 2 Outputs [CSA C22.2 No.223:2015 Ed.3]